// Description
# Schneider Electric Security Notification
11-Jun-24 Document Reference Number – SEVD-2024-163-04 Page 1 of 4
## SpaceLogic AS-P and AS-B Automation Servers
11 June 2024
## Overview
Schneider Electric is aware of multiple vulnerabilities in its SpaceLogic AS-P and AS-B products. The SpaceLogic AS-P system controller performs key functionality: control logic, trend logging & alarm supervision, and supports communication & connectivity to I/O & field buses. The Spacelogic AS-B is a compact, all-in-one server or controller for EcoStruxure Building Operation. Failure to apply the remediation provided below may risk exposure of SNMP credentials and escalation of privileges which could cause unauthorized changes to the system configuration.
## Affected Products and Versions
Product Version SpaceLogic AS-P SpaceLogic AS-B V5.0.3 and prior
## Vulnerability Details
CVE ID: CVE-2024-5558
CVSS v3.1 Base Score 6.4 | Medium | CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H
CWE-367: Time-of-check Time-of-use (TOCTOU) Race Condition vulnerability exists that could cause escalation of privileges when an attacker abuses a limited admin account. CVE ID: CVE-2024-5557
CVSS v3.1 Base Score 4.5 | Medium | CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N
CWE-532: Insertion of Sensitive Information into Log File vulnerability exists that could cause exposure of SNMP credentials when an attacker has access to the controller logs.
Note regarding vulnerability details: The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Schneider Electric Security Notification
11-Jun-24 Document Reference Number – SEVD-2024-163-04 Page 2 of 4