// Description
Schneider Electric Security Notification
11-Aug-20 Document Reference Number – SEVD-2020 -224-05 Page 1 of 4
## PowerChute Business Edition
11 August 2020
## Overview
Schneider Electric is aware of a vulnerability in the PowerChute Business Edition software which may lead to remote code execution.
## Affected Product(s)
PowerChute Business Edition software V9.0.x and earlier
## Vulnerability Details
CVE ID: CVE-2020-7526
CVSS v3.0 Base Score 7.1 | High | CVSS:3.0/AV:N/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H
A CWE-20: Improper Input Validation vulnerability exists which could cause remote code execution when a script is executed during a shutdown event.
## Remediation
This vulnerability is fixed in version V9.1 and above. The latest versions are available for download below:
https://www.apc.com/pcbe
• Update to the latest release V10.x or above (64-bit environment) or V9.5 or above (32-bit environment)
• Reboot if required at the end of software installation.
The following workarounds and mitigations can be applied by customers to reduce the risk:
• Change user login password to a secure password.
• Utilize application whitelisting software.
• Utilize firewall rules to limit access to those intended to connect. Schneider Electric Security Notification
11-Aug-20 Document Reference Number – SEVD-2020 -224-05 Page 2 of 4
## Product Information
PowerChute Business Edition software provides UPS management, graceful shutdown and innovative energy management capabilities for servers and workstations using dedicated serial or USB connections.
Product Category - Critical Power, Cooling and Racks
> Learn more about Schneider Electric’s product categories here: https://www.se.com/us/en/all-products
How to determine if you are affected
Check the currently installed version in the Help > About menu. If V9.0.x or earlier, update to the latest version available on https://www.apc.com/pcbe .