// Description
# Schneider Electric Security Notification
13-May-25 Document Reference Number – SEVD-2025-133-04 Page 1 of 3
> Public
## PrismaSeT Active - Wireless Panel Server
13 May 2025
## Overview
Schneider Electric is aware of a vulnerability disclosed in the Silicon Labs Gecko Bootloader used in the PrismaSet Active – Wireless Panel Server. The PrismaSeT Active - Wireless Panel Server product is the latest generation of low-voltage switchboards, natively connected to the cloud. Failure to apply the mitigations provided below may risk unauthorized code execution, which could result in the unavailability of the Prisma SeT Active Wireless Panel Server for Voltage loss monitoring.
## Affected Products and Versions
Product Version PrismaSeT Active - Wireless Panel Server All versions
## Vulnerability Details
A vulnerability disclosed in the Silicon Labs Gecko Bootloader impacts devices that are used in the PrismaSet Active – Wireless Panel Server. CVE ID: CVE-2023-4041
Additional information about the vulnerability CVE-2023-4041 can be found here: https://cve.mitre.org/cgi-bin/cvename.cgi?name=CVE-2023-4041
## Mitigations
Affected Product & Version Mitigations PrismaSeT Active -Wireless Panel Server
All Versions
PrismaSeT Active - Wireless Panel Server product has reached its end of life and is no longer supported. Customers should immediately apply the following mitigations to reduce the risk of exploit:
> •
Deactivate Bluetooth Low (BLE) communication of Wireless Panel Server when it is not in use.
> •
Periodically review audit logs and/or EcoStruxure™ Facility Expert App security notifications to detect unexpected behaviors.
> •
Regularly check the physical security of the Wireless Panel Server to protect against unauthorized Bluetooth pairing. Schneider Electric Security Notification
13-May-25 Document Reference Number – SEVD-2025-133-04 Page 2 of 3
> Public
> •