IM
IronMonkey Threat Research
‹ Back to ICS Advisories

PowerLogic P5

MEDIUM
CVSS 6.1
Date 2026-10-16T20:33:36+00:00
Source schneider-electric
Published by Schneider Electric

// Description

# Schneider Electric Security Notification > 11-Jun-24 (10-Sep-24) Document Reference Number – SEVD-2024 -163-02 (v1.2.0) Page 1 of 4 ## PowerLogic P5 11 June 2024 (10 September 2024) Overview Schneider Electric is aware of a vulnerability in its PowerLogic P5 products. The PowerLogic P5 is a medium voltage protection relay. Failure to apply the mitigations provided below may risk denial of service, device reboot, or an attacker gaining full control of the relay. This could result in loss of protection to your electrical network. Physical access to the device is required to exploit this issue. September 2024: Remediation for PowerLogic P5 is now available. Affected Products and Versions Product Version PowerLogic P5 v01.500.104 and prior Vulnerability Details CVE ID: CVE-2024-5559 CVSS v3.1 Base Score 6.1 | Medium | CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists that could cause denial of service, device reboot, or an attacker gaining full control of the relay when a specially crafted reset token is entered into the front panel of the device. Note regarding vulnerability details: The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment. Schneider Electric Security Notification > 11-Jun-24 (10-Sep-24) Document Reference Number – SEVD-2024 -163-02 (v1.2.0) Page 2 of 4 Remediation Affected Product & Version Remediation PowerLogic P5 v01.500.104 and prior

// Vulnerabilities (1)

CVE ID CVSS Score Severity Description
CVE-2024-5559 6.1 medium
CVE-2024-5559. CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists that could cause denial of service, device reboot, or an attacker gaining full control of the relay when a specially crafted reset token is entered into the front panel of the device.

// Remediations (1)

Patch: PowerLogic P5 Wave 4.2.3 P5L30 firmware includes a fix for this vulnerability. Contact Schneider Ele
PowerLogic P5 Wave 4.2.3 P5L30 firmware includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center to download this firmware.

// References