# Schneider Electric Security Notification 11-Jun-24 (09-Jul-24) Document Reference Number – SEVD-2024 -163-05 (v2.0.0) Page 1 of 5 ## SAGE RTU 11 June 2024 (9 July 2024) ## Overview Schneider Electric is aware of multiple vulnerabilities in its SAGE RTU products. The SAGE RTU products are hardware devices that collect utility substation information from different devices and passes it along to a SCADA software platform. Failure to apply the remediation provided below may risk total compromise of the impacted device, leading to loss of data, loss of operation, or impacts to the performance of the device. July 2024 Update: A direct link is now available to the remediation. ## Affected Products and Versions Product Version Sage 1410 Sage 1430 Sage 1450 Sage 2400 Sage 3030 Magnum Sage 4400 Versions C3414-500-S02K5_P8 and prior ## Vulnerability Details CVE ID: CVE-2024-37036 CVSS v3.1 Base Score 9.8 | Critical | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H CWE-787: Out-of-bounds Write vulnerability exists that could result in an authentication bypass when sending a malformed POST request and particular configuration parameters are set. CVE ID: CVE-2024-37037 CVSS v3.1 Base Score 8.1 | High | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H CWE-22: Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) vulnerability exists that could allow an authenticated user with access to the device’s web interface to corrupt files and impact device functionality when sending a crafted HTTP request. CVE ID: CVE-2024-37038 CVSS v3.1 Base Score 7.5 | High | CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H Schneider Electric Security Notification 11-Jun-24 (09-Jul-24) Document Reference Number – SEVD-2024 -163-05 (v2.0.0) Page 2 of 5

// Vulnerabilities (6)

CVE ID CVSS Score Severity Description
CVE-2024-37037 9.8 critical
CVE-2024-37037. CWE-22: Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) vulnerability exists that could allow an authenticated user with access to the device’s web interface to corrupt files and impact device functionality when sending a crafted HTTP request.
CVE-2024-37036 9.8 critical
CVE-2024-37036. CWE-787: Out-of-bounds Write vulnerability exists that could result in an authentication bypass when sending a malformed POST request and particular configuration parameters are set.
CVE-2024-37040 9.8 critical
CVE-2024-37040. CWE-120: Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’) vulnerability exists that could allow a user with access to the device’s web interface to cause a fault on the device when sending a malformed HTTP request.
CVE-2024-5560 9.8 critical
CVE-2024-5560. CWE-125: Out-of-bounds Read vulnerability exists that could cause denial of service of the device’s web interface when an attacker sends a specially crafted HTTP request.
CVE-2024-37038 9.8 critical
CVE-2024-37038. CWE-276: Incorrect Default Permissions vulnerability exists that could allow an authenticated user with access to the device’s web interface to perform unauthorized file and firmware uploads when crafting custom web requests.
CVE-2024-37039 9.8 critical
CVE-2024-37039. CWE-252: Unchecked Return Value vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request.

// Remediations (1)

Patch: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is avai
Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/