// Description
# Schneider Electric Security Notification
> 08-Jun-21 (12-Nov-24) Document Reference Number – SEVD-2021-159-02 (v2.0.0) Page 1 of 5
## PowerLogic PM5500 and PowerLogic PM8ECC
8 June 2021 (12 November 2024)
## Overview
Schneider Electric is aware of a vulnerability in its PowerLogic PM55xx and PowerLogic PM8ECC products. The PowerLogic PM55xx products are power metering devices. The PowerLogic PM8ECC product is an ethernet communication module. Failure to apply the mitigations or remediations provided below may risk elevation of privileges, which could result in loss of control of the affected device. Update November 2024: Remediation is now available for PM5562.
## Affected Products and Versions
CVE Product Version CVE-2021-22763 CVE-2021-22764 PM5560 Versions prior to v2.7.8 PM5561 Versions prior to v10.7.3 PM5562 v2.5.4 and prior PM5563 Versions prior to v2.7.8 CVE-2021-22763 PM8ECC All versions
## Vulnerability Details
CVE ID: CVE-2021-22763
CVSS v3.1 Base Score 8.1 | High | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H
CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could allow an attacker administrator level access to a device. CVE ID: CVE-2021-22764
CVSS v3.1 Base Score 5.3 | Medium | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
CWE-287: Improper Authentication vulnerability exists that could cause loss of connectivity to the device via Modbus TCP protocol when an attacker sends a specially crafted HTTP request. Schneider Electric Security Notification
> 08-Jun-21 (12-Nov-24) Document Reference Number – SEVD-2021-159-02 (v2.0.0) Page 2 of 5