// Description
# Schneider Electric Security Notification
14-Jan-25 Document Reference Number – SEVD-2025-014-08 Page 1 of 4
# PowerLogic™ HDPM6000 High-Density Metering System
14 January 2025
## Overview
Schneider Electric is aware of multiple vulnerabilities in its PowerLogic™ HDPM6000 High-Density Metering System product. The HDPM6000 products are high-density, multi-circuit busway and panelboard power meters for cost and network management in large and critical power applications. Failure to apply the remediation provided below may risk a low privileged user gaining higher level access, which could allow for modification of system configuration parameters or an unauthenticated user causing data corruption or denial of service to the devices web interface via a specially crafted Modbus protocol write operation.
## Affected Products and Versions
Product CVE-2024-10497 CVE-2024-10498 PowerLogic™ HDPM6000 Version v0.62.7 only Versions v0.62.7 and prior
## Vulnerability Details
CVE ID: CVE-2024-10497
CVSS v3.1 Base Score 8.8 | High | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
CVSS v4.0 Base Score 8.7 | High | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CWE-639: Authorization Bypass Through User-Controlled Key vulnerability exists that could allow an authorized attacker to modify values outside those defined by their privileges (Elevation of Privileges) when the attacker sends modified HTTPS requests to the device. CVE ID: CVE-2024-10498
CVSS v3.1 Base Score 6.5 | Medium | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L
CVSS v4.0 Base Score 6.9 | Medium | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:L/SC:N/SI:N/SA:N