IM
IronMonkey Threat Research

CVE-2022-28613 HIGH

Published: 2022-05-02 | Last Modified: 2024-11-21 | Status: Modified

Description

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Additional Descriptions (1)

Una vulnerabilidad en el COMPONENTE HCI Modbus TCP del firmware de la CMU de la serie RTU500 de Hitachi Energy, causada por un error de comprobación en la información de longitud que se transmite en el encabezado MBAP, permite a un ATACANTE reiniciar el dispositivo mediante el envío de un mensaje especialmente diseñado. Este problema afecta a: Hitachi Energy RTU500 series CMU Firmware versiones 12.0.*; 12.2.*; 12.4.*; 12.6.*; 12.7.*; 13.2.*

CVSS Metrics

Base Score: 7.5 (HIGH)

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Attack VectorNETWORK
Attack ComplexityLOW
Privileges RequiredNONE
User InteractionNONE
ScopeUNCHANGED
Confidentiality ImpactNONE
Integrity ImpactNONE
Availability ImpactHIGH

Source: [email protected]

Type: Primary

Exploitability Score: 3.9

Impact Score: 3.6

Base Score: 7.8 (HIGH)

AV:N/AC:L/Au:N/C:N/I:N/A:C

Access VectorNETWORK
Access ComplexityLOW
AuthenticationNONE
Confidentiality ImpactNONE
Integrity ImpactNONE
Availability ImpactCOMPLETE

Source: [email protected]

Type: Primary

Exploitability Score: 10.0

Impact Score: 6.9

Weaknesses

Source Type Description
[email protected] Secondary
en CWE-1284
[email protected] Primary
en CWE-1284

Affected Products

Vendor Product Version Update Type
abb rtu500_firmware * <built-in method update of dict object at 0x72a9ccfed480> Operating System
hitachienergy rtu500_firmware * <built-in method update of dict object at 0x72a9ccfee680> Operating System
hitachienergy rtu500_firmware * <built-in method update of dict object at 0x72a9ccfec6c0> Operating System
hitachienergy rtu500_firmware * <built-in method update of dict object at 0x72a9cdbff700> Operating System
hitachienergy rtu500_firmware * <built-in method update of dict object at 0x72a9cdbfc480> Operating System
hitachienergy rtu500_firmware * <built-in method update of dict object at 0x72a9cc64c8c0> Operating System

Affected Configurations

Operator: OR

Vulnerable CPE
Yes cpe:2.3:o:abb:rtu500_firmware:*:*:*:*:*:*:*:*
Yes cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*
Yes cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*
Yes cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*
Yes cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*
Yes cpe:2.3:o:hitachienergy:rtu500_firmware:*:*:*:*:*:*:*:*

Operator: OR

Vulnerable CPE
No cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*
Notification